Diaphragm solenoid valve
Voltage and principle | Change voltage | Fast. voltage | ||
Normally closed | Normally open | Normally closed | Normally open | |
With threads. connection | DP-16 | DP-12C-DP-16C | DP-12D-DP-16D | DP-12CD-DP-16CD |
With flange. connection | DP-18 | DP-14C-DP-18C | DP-14D-DP-18D | DP-14CD-DP-18CD |
Model | AC coil current | - | - | DP-12C | DP-14C |
DC coil current | DP-12D | DP-14D | DP-12CD | DP-14CD | |
Application | Air, cold and hot water, oil (up to 20 cSt) | ||||
Operating pressure | 0-1.0 MPa (does not work during evacuation) | ||||
Min. differential pressure | 0 MPa (requires at least 0.1 MPa in case of vertical mounting) | ||||
Leaking valve seat | There is no leakage from the pressure gauge | ||||
Max. temperature | 60 ° C | ||||
Principle | Normally closed | Normally open | |||
Material | Frame | Cast bronze | |||
Valve | Nitrile butadiene rubber (membrane) | ||||
Compound | JIS Rc Threaded Connection | Flange connection JIS 10K FF | JIS Rc Threaded Connection | Flange connection JIS 10K FF |
Model | AC coil current | DP-16 | DP-18 | DP-16C | DP-18C |
DC coil current | DP-16D | DP-18D | DP-16CD | DP-18CD | |
Application | Air, cold and hot water, oil (up to 20 cSt) | ||||
Operating pressure | 0-1.0 MPa (does not work during evacuation) | ||||
Min. differential pressure | 0 MPa (requires at least 0.1 MPa in case of vertical mounting) | ||||
Leaking valve seat | There is no leakage from the pressure gauge | ||||
Max. temperature | 60 ° C | ||||
Principle | Normally closed | Normally open | |||
Material | Frame | Cast stainless steel | |||
Valve | Nitrile butadiene rubber (membrane) | ||||
Compound | Threaded JIS Rc | Flanged JIS 10K FF | Threaded JIS Rc | Flanged JIS 10K FF |
• Available with FPM components.
* Available with terminal box (plastic).
The solenoid valve is opened and closed by moving a steel element called a plunger under the influence of solenoid electromagnetic forces and is used to control the flow of fluid in pipelines (open-close control).
- Exceptional corrosion resistance is ensured by wetted parts made of stainless steel.
- Installation in horizontal and vertical positions.
Model DP-16
Nom. the size | d | L | H | H 1 | The weight |
15A | Rc 1/2 | 70 | 109.5 | 14.5 | 1.1 |
20A | Rc 3/4 | 80 | 116.5 | 17.5 | 1,3 |
25A | Rc 1 | 95 | 123.5 | 21.0 | 1.7 |
32A | Rc 1-1 / 4 | 110 | 150.5 | 26.0 | 2.5 |
40A | Rc 1-1 / 2 | 120 | 157.5 | 29.5 | 3.1 |
50A | Rc 2 | 140 | 172.5 | 36.5 | 5.0 |
Models DP-12C, 16C (DP-16C: 15A-50A)
Nom. the size | d | L | H | H 1 | The weight |
10A | Rc 3/8 | 70 | 172 | 14.5 | 1.4 |
15A | Rc 1/2 | 70 | 172 | 14.5 | 1.4 |
20A | Rc 3/4 | 80 | 179 | 17.5 | 1.6 |
25A | Rc 1 | 95 | 186 | 21.0 | 2.0 |
32A | Rc 1-1 / 4 | 110 | 213 | 26.0 | 2.8 |
40A | Rc 1-1 / 2 | 120 | 220 | 29.5 | 3.4 |
50A | Rc 2 | 140 | 235 | 36.5 | 5.3 |
Models DP-12D, 16D, (DP-16D: 15A-50A)
Nom. the size | d | L | H | H 1 | The weight |
10A | Rc 3/8 | 70 | 124 | 14.5 | 1.9 |
15A | Rc 1/2 | 70 | 124 | 14.5 | 1.9 |
20A | Rc 3/4 | 80 | 131 | 17.5 | 2.1 |
25A | Rc 1 | 95 | 138 | 21.0 | 2.5 |
32A | Rc 1-1 / 4 | 110 | 166 | 26.0 | 3.3 |
40A | Rc 1-1 / 2 | 120 | 173 | 29.5 | 3.9 |
50A | Rc 2 | 140 | 187 | 36.5 | 5.8 |
DP-12CD models. 16CD, (DP-16CD: 15A-50A)
Nom. the size | d | L | H | H 1 | The weight |
10A | Rc 3/8 | 70 | 172 | 14.5 | 2.1 |
15A | Rc 1/2 | 70 | 172 | 14.5 | 2.1 |
20A | Rc 3/4 | 80 | 179 | 17.5 | 2,3 |
25A | Rc 1 | 95 | 186 | 21.0 | 2.7 |
32A | Rc 1-1 / 4 | 110 | 213 | 26.0 | 3.5 |
40A | Rc 1-1 / 2 | 120 | 220 | 29.5 | 4.1 |
50A | Rc 2 | 140 | 235 | 36.5 | 6.0 |
Model DP-18
Nom. the size | d | L | H | H 1 | The weight |
15A | 15 | 120 | 142.5 | 47.5 | 2.6 |
20A | twenty | 130 | 149.0 | 50.0 | 3.2 |
25A | 25 | 145 | 165.0 | 62.5 | 4.7 |
32A | 32 | 160 | 192.0 | 67.5 | 6.5 |
40A | 40 | 170 | 198.0 | 70.0 | 7.2 |
50A | 50 | 195 | 213.0 | 77.5 | 9.9 |
Models DP-14C, 18C
Nom. the size | d | L | H | H 1 | The weight |
15A | 15 | 120 | 205 | 47.5 | 2.9 |
20A | twenty | 130 | 212 | 50.0 | 3.5 |
25A | 25 | 145 | 228 | 62.5 | 5.0 |
32A | 32 | 160 | 255 | 67.5 | 6.8 |
40A | 40 | 170 | 261 | 70.0 | 7.5 |
50A | 50 | 195 | 276 | 77.5 | 10.2 |
Models DP-14D, 18 D
Nom. the size | d | L | H | H 1 | The weight |
15A | 15 | 120 | 157 | 47.5 | 3.4 |
20A | twenty | 130 | 164 | 50.0 | 4.0 |
25A | 25 | 145 | 180 | 62.5 | 5.5 |
32A | 32 | 160 | 207 | 67.5 | 7.3 |
40A | 40 | 170 | 213 | 70.0 | 8.0 |
50A | 50 | 195 | 228 | 77.5 | 10,7 |
DP-14CD models. 18 CD
Nom. the size | d | L | H | H1 | The weight |
15A | 15 | 120 | 205 | 47.5 | 3.6 |
20A | twenty | 130 | 212 | 50.0 | 4.2 |
25A | 25 | 145 | 228 | 62.5 | 5.7 |
32A | 32 | 160 | 255 | 67.5 | 7.5 |
40A | 40 | 170 | 261 | 70.0 | 8.2 |
50A | 50 | 195 | 276 | 77.5 | 10.9 |
Nominal sizing diagram (for air)
How to use a chart
When selecting the nominal size of the solenoid valve at inlet pressure (P1), outlet pressure (P2) and air flow (Q) (20 ° C) 0.5 MPa, 0.35 MPa and 600 m3 / h (standard conditions), accordingly, first find the point of intersection (a) of the lines P1 = 0.5 MPa and P2 = 0.35 MPa. Draw a vertical line downward from this point (a) to the point of intersection (b) with the line Q = 600 m3 / h (standard conditions). Since this intersection point (b) lies between the nominal sizes 20A and 25A, choose the larger of the two, 25A.
Nominal sizing diagram (for water)
How to use a chart
When selecting the nominal size of the solenoid valve with inlet pressure (P1), outlet pressure (P2) and flow (V) 0.7 MPa, 0.5 MPa and 300 l / min, respectively, first find the intersection point (a) of the lines differential pressure (∆P = 0.7 - 0.5 = 0.2 MPa) and V = 300 l / min. Since this intersection point (a) lies between dimensions 25A and 32A, choose the larger of the two, 32A.
Delivery
- Pickup from a warehouse in Kiev - is free
- New Mail - at the rates of the delivery service, at the rates of the delivery service, at the rates of the delivery service
- SAT - at the rates of the delivery service
- Deliveri - at the rates of the delivery service
Payment
- Cashless payment with VAT
- Online Privat24, Visa / MasterCard