Application | Heating system tank with reinforced insulation to avoid heat loss. One or two spiral heat exchangers (depending on version) for bioenergy plants, solar collectors or other external heat sources. |
Execution | Made of high quality S235JR EN10025 carbon steel, assembled and welded by automatic welding. Heat exchanger: Non-removable spiral heat exchangers welded to the tank with S235JR EN10025 carbon steel tubes. PS: tank without heat exchangers. PSR: tank with one non-removable heat exchanger. PSRR: tank with two non-removable heat exchangers. |
Anti-corrosion coating | External coating against corrosion. |
Insulation and type of outer cover | For mod. with a capacity of 200 to 500 liters - rigid polyurethane insulation, and for the rest - flexible polyurethane insulation, PVC outer cover with zipper and thermal cover. |
Certificates | Complies with directive 97/23 / CE Art. 3 - Part 3. |
Model | 200 | 300 | 500 | 800 | 1000 | 1500 | 2000 | 2500 | 3000 | 4000 | 5000 | ||
Tank capacity | l | 184 | 294 | 485 | 796 | 918 | 1465 | 1996 | 2559 | 2946 | 3802 | 5033 | |
d | Actual tank capacity | mm | 450 | 550 | 650 | 790 | 790 | 950 | 1100 | 1250 | 1250 | 1400 | 1600 |
D | Insulated diameter | mm | 550 | 650 | 750 | 990 | 990 | 1150 | 1300 | 1450 | 1450 | 1600 | 1800 |
HT | Height | mm | 1300 | 1350 | 1630 | 1805 | 2055 | 2280 | 2330 | 2420 | 2670 | 2760 | 2810 |
Heating area of the spiral heat exchanger mod. PSR | m 2 | - | 1.50 | 2.40 | 2.60 | 3.00 | 4.10 | 4.50 | 4.80 | 5.30 | 6.10 | 7.10 | |
Heating area of the lower spiral Heat exchanger mod. PSRR | m 2 | - | 1.50 | 2.40 | 2.60 | 3.00 | 4.10 | 4.50 | 4.80 | 5.30 | 6.10 | 7.10 | |
Heating area of the upper spiral Heat exchanger mod. PSRR | m 2 | - | 1.00 | 1.90 | 2.60 | 3.00 | 4.10 | 4.50 | 4.80 | 5.30 | 6.10 | 7.10 | |
TO | Maximum tilt height | mm | 1409 | 1498 | 1794 | 2058 | 2281 | 2535 | 2668 | 2821 | 3028 | 3190 | 3337 |
Tank weight mod. PS | Kg | 55 | 65 | 85 | 130 | 165 | 226 | 270 | 325 | 380 | 435 | 540 | |
Tank weight mod. PSR | Kg | - | 85 | 120 | 160 | 190 | 270 | 310 | 360 | 420 | 520 | 650 | |
Tank weight mod. PSRR | Kg | - | 100 | 135 | 190 | 210 | 300 | 350 | 410 | 450 | 590 | 720 | |
Connections | |||||||||||||
A | Standard connection | G1 "¼ | G1 "¼ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | |
B | Standard connection | G1 "¼ | G1 "¼ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | |
Sf | Discharge pipe | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | |
S1S2 | Lower spiral heat exchanger connections | - | G "M | G "M | G "M | G "M | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | |
S3 S4 | Upper spiral heat exchanger connections (for mod. PSRR) | - | G1 " | G1 " | G1 " | G1 " | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | |
Technical details | |||||||||||||
PE | Maximum working pressure of the tank | bar | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
PC | Tank test pressure | bar | nine | nine | nine | nine | nine | nine | nine | nine | nine | nine | nine |
TE | Max. working temperature | ° C | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
PS | Maximum working pressure of the heat exchanger | bar | - | nine | nine | nine | nine | nine | nine | nine | nine | nine | nine |
PCS | Heat exchanger test pressure | bar | - | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen |
Delivery
- Pickup from a warehouse in Kiev - is free
- New Mail - at the rates of the delivery service, at the rates of the delivery service, at the rates of the delivery service
- SAT - at the rates of the delivery service
- Deliveri - at the rates of the delivery service
Payment
- Cashless payment with VAT
- Online Privat24, Visa / MasterCard