Model |
|
| 200 | 300 | 500 | 800 | 1000 | 1500 | 2000 | 2500 | 3000 | 4000 | 5000 |
| Volume | l | 185 | 295 | 500 | 795 | 920 | 1435 | 1980 | 2605 | 2910 | 3710 | 4945 |
d | Diameter without insulation | mm | 450 | 550 | 650 | 800 | 800 | 950 | 1100 | 1250 | 1250 | 1400 | 1600 |
D | Insulated diameter | mm | 550 | 650 | 750 | 900 | 900 | 1050 | 1200 | 1350 | 1350 | 1500 | 1700 |
HT | Height | mm | 1370 | 1420 | 1730 | 1810 | 2060 | 2390 | 2430 | 2500 | 2750 | 2800 | 2830 |
L | Length (horizontal design) | mm | 1310 | 1390 | 1670 | 1730 * | 1980 | 2300 | 2370 | 2440 | 2680 | 2780 | 2860 |
IS | Distance between supports (horizontal version) | mm | 840 | 840 | 1090 | 1010 | 1230 | 1510 | 1510 | 1470 | 1720 | 1720 | 1720 |
FL | Inspection hatch diameter (QB / X, XN / X) | mm | 220 × 300 | 300 × 380 | 350 × 430 |
SS1 | Tubular heat exchanger heating area (QB / X) | m 2 | 0.50 | 0.75 | 1.00 | 1.50 | 2.00 | 3.00 | 4.00 | 5.00 | 6.00 | 8.00 | 10.00 |
FL | Inspection hatch diameter (HBX) | mm | - | - | - | 220 × 300 | 400 × 480 |
SS1 | Tubular Heat Exchanger Heating Area (HBX) | m 2 | - | - | - | 1.50 | 2.00 | 3.00 | 4.00 | 5.00 | 6.00 | 8.00 | 10.00 |
K | Maximum tilt height | mm | 1557 | 1625 | 1922 | 2079 | 2307 | 2592 | 2701 | 2823 | 3045 | 3176 | 3305 |
| Weight, 6 bar | Kg | - | - | - | - | - | 240 | 295 | 345 | 380 | 555 | 660 |
| Weight, 8 bar | Kg | 60 | 75 | 90 | 135 | 175 | 300 | 365 | 430 | 475 | 770 | 790 |
| Weight, 10 bar | Kg | 75 | 95 | 115 | 175 | 200 | 360 | 440 | 515 | 565 | 895 | 915 |
| Connections |
|
|
|
|
E | Cold water inlet |
| G1 "¼ | G1 "¼ | G1 "¼ | G1 "½ | G1 "½ | G2 " | G2 " | G2 "½ | G2 "½ | G3 " | G3 " |
U | Hot water outlet |
| G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G2 " | G2 " | G2 "½ | G2 "½ | G3 " | G3 " |
RC | Recirculation |
| G1 "¼ | G1 "¼ | G1 "¼ | G1 "½ | G1 "½ | G2 " | G2 " | G2 "½ | G2 "½ | G3 " | G3 " |
RE | Electric heating element |
| G1 "¼ | G1 "¼ | G1 "¼ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G2 " | G2 " | G2 " | G2 " |
P | Heating circuit |
| G1 " | G1 " | G1 " | G1 "½ | G1 "½ | G1 "½ | G2 " | G2 " | G2 " | G2 " | G2 " |
S | Draining |
| G½ " | G½ " | G½ " | G½ " | G½ " | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ | G1 "¼ |
A | Magnesium anode |
| G1 "¼ | G1 "¼ | G1 "¼ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ | G1 "½ |
T | Thermometer / thermostat |
| G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " |
AE | Electronic anode |
| - | - | - | - | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " |
So | Sensor |
| G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " | G½ " |
| Technical details |
|
|
|
|
PE | Maximum working pressure of the tank | bar | eight | eight | eight | eight | eight | 6 | 6 | 6 | 6 | 6 | 6 |
PC | Tank test pressure | bar | 12 | 12 | 12 | 12 | 12 | nine | nine | nine | nine | nine | nine |
| Maximum working pressure of the heat exchanger | bar | nine | nine | nine | nine | nine | nine | nine | nine | nine | nine | nine |
| Heat exchanger test pressure | bar | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen | fourteen |
TE | Continuous operating temperature (QB / X) | ° C | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 |
TE | Peak temperature (QB / X) | ° C | 81 | 81 | 81 | 81 | 81 | 81 | 81 | 81 | 81 | 81 | 81 |
TE | Maximum operating tank temperature (XN / X, HBX) | ° C | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
TE | Maximum operating temperature of the heat exchanger | ° C | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |