Parameter name | Meaning | |||
Model | OB-4 | OB-4G | ||
Application | Cooling | Cold water, refrigerant | ||
Cooling Wednesday | Cold and hot water, oil, other non-hazardous liquids | |||
Max. pressure | Frame | 15A-40A: 0.7 MPa (1.0 MPa) 50A: 0.5 MPa (0.7 MPa) 65A: 0.5 MPa (0.7 MPa) 80A: 0.4 MPa (0.5 MPa) 100A: 0.4 MPa 125A: 0.2 MPa (0.35 MPa for OB-2) 150A: 0.2 MPa | ||
Thermal valve | 1.0 MPa | |||
Max. temperature | 180 ° C | |||
Setting range temp. | For liquid | 40-120 ° C | 15-100 ° C | |
For air | 40-120 ° C | 15-100 ° C | ||
Pace. surrounded Wednesday | Setting temperature -10 ° or less | Setting temperature 30 ° or less | ||
Material | Frame | Cast iron | ||
Valve, valve seat | Phosphor bronze (stainless steel) | |||
Valve stem | Stainless steel | |||
Bellows | Phosphor bronze | |||
Thermo valve | For liquid | Stainless steel | ||
For air | Stainless steel | |||
Std. capillary length | 15A-80A: 2m 100A-150A: 3m | |||
Compound | Flange connection JIS 10K FF |
- If the ambient temperature is above the set temperature or below 40 ° C, use OB-4G (with external pressure bellows).
- Available with capillary tube up to 5 m.
- Available with a maximum temperature within []. (Valve mechanism and seat materials and bellows are different from the standard model.)
- Available with sleeve (SUS304 or PTFE cap) for fluid.
Temperature setting range
OB-4
Setting range temp. (° C) | Withstanding temperature (° С) | |
For liquid | For air | |
40-60 | 40-60 | 70 |
50-70 | 50-70 | 80 |
60-80 | 60-80 | 90 |
80-100 | 80-100 | 110 |
100-120 | 100-120 | 130 |
- The term withstand temperature refers to the maximum temperature at which the bellows can withstand internal pressure.
- Options with a temperature control range of 30 ° C are available (only OB-4).
OB-4G
Setting range temp. (° C) | Maintained pace. (° C) | |
For liquid | For air | |
15-35 | 15-35 | 50 |
20-40 | 20-40 | 50 |
35-55 | 35-55 | 70 |
40-60 | 40-60 | 90 |
50-70 | 50-70 | 100 |
60-80 | 60-80 | 110 |
70-90 | 70-90 | 120 |
80-100 | 80-100 | 130 |
The term withstand temperature refers to the maximum temperature at which the bellows can withstand internal pressure.
- No additional adjustment tool is required, the regulator is equipped with a knob for setting the temperature.
- Thanks to the double valve, the operating flow range of these models is wider.
- Exceptional precision thanks to a special stem packing that influences the opening / closing of the valve.
- The OB-4G model offers excellent thermal stability thanks to the external pressure bellows.
Nom. the size | L | H 1 | H | The weight |
15A | 126 | 60 | 520 | 15 |
20A | 130 | 60 | 520 | 16 |
25A | 140 | 70 | 540 | eighteen |
32A | 150 | 75 | 550 | 21 |
40A | 160 | 75 | 550 | 23 |
50A | 180 | 110 | 620 | 29 |
65A | 215 | 125 | 650 | 38 |
80A | 260 | 135 | 700 | 48 |
100A | 300 | 160 | 750 | 58 |
125A | 360 | 190 | 810 | 76 |
150A | 382 | 220 | 980 | 125 |
How to use a chart
If the inlet pressure is 0.3 MPa, the outlet pressure is 0.15 MPa, the flow rate is 9 m3 / h, find the intersection point (a) of the differential pressure lines (∆Р = 0.15 MPa) (0.3 MPa - 0.15 MPa) and a flow rate of 9 m3 / h. Since this intersection point (a) lies between dimensions 32A and 40A, choose the larger of the two, 40A.
* The flow chart is for reference.