  • Manufacturer: Yoshitake (Japan)
  • Material: ductile iron, stainless steel
  • Action type: pilot operated
Quick order
Enter your phone number and
our manager will call you back
  • Specifications
  • Description
  • Dimensions and weight
  • Delivery and payment
ModelGP-2000EN
ApplicationSteam
Low pressure sensing methodExternal Impulse Piping * 1
Inlet pressure0.1-2.0 MPa
Under pressure0.02-0.15 MPa 0.1-1.4 MPa 1.3-1.7 MPa
Up to 85% of inlet pressure (gauge)
Min. differential pressure0.05 MPa
Max. coeff. pressure reduction20: 1
Maximum temperature220 ° C
Valve seat leaksNot more than 0.01% of nominal flow
MaterialCorpusDuctile iron
Main valvest. steel
Valve seatst. steel
Pilot Valvest. steel
Pilot seatst. steel
-MembraneStainless steel
Reduced pressure impulse tubingCopper pipe 0.8-2 m
ConnectionFlanged EN 1092 PN25

Pilot diaphragm valve control with high-precision low pressure regulation. This option is optimal if pressure surges significantly affect quality.

* 1. Standard external impulse tube. When installing a pressure relief valve, be sure to attach the supplied impulse pipe and compensator. If the impulse line is not connected, the valve will not work. (Available with internal impulse pipe (nominal diameter: 15 A to 10 A) in different specifications. Note that the Cv value in the pipe in the inner impulse pipe is lower than in the external impulse pipe.)

- Remote pilot options available. & nbsp;

- ASME flange options available.

Yoshitake GP-2000EN Steam Reducing Valve

Yoshitake GP-2000EN Steam Reducing Valve

  1. Large diaphragm; more stable reduced pressure regulation with external impulse tube.
  2. The Cv value is high, so the flow capacity and control ability are greatly improved; one or two sizes smaller than nominal can be used.
  3. Spherical main valve provides good sealing and reduced leakage and valve seat (ANSI Class IV).
  4. Low pressure pressure control (0.02 MPa or less) is possible.

Threaded versions

No. size d L H 1 H A Weight
15A Rc 1/2 150 170 398 200 14.0
20A Rc 3/4 150 170 398 200 14.0
25A Rc 1 160 175 404 226 18.5
32A Rc 1-1 / 4 180 192 434 226 21.5
40A Rc 1-1 / 2 180 192 434 226 21.5
50A Rc 2 230 216 498 276 33.0

* NPT options available.

Flanged (JIS 20K RF)

No. size L H1 H A Weight
15A 146 (142) 170 398 200 15.5 (15.3)
20A 146 (142) 170 398 200 16.0 (15.8)
25A 156 (152) 175 404 226 21.0 (20.6)
32A 176 (172) 192 434 226 24.0 (23.6)
40A 196 (192) 192 434 226 24.5 (24.1)
50A 222 (218) 216 498 276 36.0 (35.8)
65A 282 (278) 251 552 352 64.5 (64.2)
80A 302 (294) 264 575 352 71.5 (68.8)
100A 342 (330) 321 658 401 111.0 (106.9)
125A 400 (388) 321 658 401 115.0 (112.0)
150A 465 (453) 414 814 502 234.3 (230.0)
200A 469 (469) 414 814 502 242.0 (238.0)

* The above values ​​in brackets are JIS 10K FF flange dimensions.

Yoshitake GP-2000EN schemas

Delivery

  • Pickup from a warehouse in Kiev - is free
  • New Mail - at the rates of the delivery service, at the rates of the delivery service, at the rates of the delivery service
  • SAT - at the rates of the delivery service
  • Deliveri - at the rates of the delivery service

Payment

  • Cashless payment with VAT
  • Online Privat24, Visa / MasterCard
Reducing valve for steam Yoshitake GP2000EN

All equipment catalog

Sorting
ApplyReset
Close
loading
loading