| Model | TF-2 | |
| Application | Steam condensation | |
| Working pressure & nbsp; (Max working differential pressure) | 0.01-0.7 MPa | |
| Max. temperature | 170 ° C | |
| Material | Corpus | Ductile iron |
| Float | Stainless steel | |
| Valve, valve seat | Stainless steel | |
| Connection | JIS Rc Thread | |
1. Stainless steel valve disc and valve seat provide excellent wear resistance (TF-2).
2. Built-in air vent prevents air problems for greater durability.
3. Reliable operation and high throughput thanks to the float arm system. &Nbsp;
TF-2
| Nominal size | d | L | H | H 1 | H 2 | Weight |
| 15A | Rc 1/2 | 257 | 252 | 122 | 42 | 13.3 |
| 20A | Rc 3/4 | 257 | 252 | 122 | 42 | 13.3 |
| 25A | Rc 1 | 290 | 266 | 122 | 42 | 15.5 |
| 32A | Rc 1-1 / 4 | 290 | 266 | 122 | 42 | 15.5 |
| 40A | Rc 1-1 / 2 | 335 | 310 | 159 | 45 | 19.2 |
| 50A | Rc 2 | 335 | 310 | 159 | 45 | 19.2 |
picture >
Maximum Continuous Performance
| Nominal size | Working differential pressure (MPa) | |||||
| 0.05 | 0.10 | 0.15 | 0.20 | 0.25 | 0.30 | |
| 65A | 6,500 | 8,700 | 10,000 | 11,000 | 13,000 | 13,000 |
| 80A | 6,500 | 8,700 | 10,000 | 11,000 | 13,000 | 13,000 |
* The bandwidth shown in the table and graph is the maximum value. When designing your system, select a steam trap with sufficient safety factor (more than three to five times the normal level).
* Choose a steam trap with a safety factor of two to three times the normal level.
Delivery
- Pickup from a warehouse in Kiev - is free
- New Mail - at the rates of the delivery service, at the rates of the delivery service, at the rates of the delivery service
- SAT - at the rates of the delivery service
- Deliveri - at the rates of the delivery service
Payment
- Cashless payment with VAT
- Online Privat24, Visa / MasterCard